                                                                       INSTRUMENT TRANSFORMER & SWITCHGEAR TEST SET
 
HOME  |  PROFILE  | PRODUCT  |  CLIENTS  |  CONTACT  |  FEEDBACK

     Apart from manufacturing the mentioned test sets, we also manufacture equipment according to 
  specific requirements of customer. 
  

                                  Instrument transformer (CT & PT) test set

 CT TEST SET

 
A] CT TEST BRIDGE:

  This test bridge is suitable for testing current transformer having secondary current of 5A and 1A.

  Input Voltage                    :           230V, 50Hz. , 1 phase AC.   
  Secondary Current             :           5A and 1A.   
  Phase Angle Error Range      :           0 to + 20 minutes on x1 range

                                                
   0 to + 100 minutes on x5 range
                                                
   0 to + 400 minutes on x20 range

  Ratio Error Range               :           0 to  + 0.5% on x1 range
                                            
       0 to  + 2.5% on x5 range
                                       
            0 to  +10% on x20 range

  Polarity Check                   :           Polarity indicated by lamp with "check" position selection.
  Ammeter                          :           One digital ammeter to indicate the injected current in %.   
  
 
Detector                          :           A built-in detector of electronic type.
 

 Test Bridge having secondary current of 5 Amps. only is also manufactured.


C. T. Test Set

B] burden box: 

  Rated current    :
            5 Amps., 1 Amps.
  Power factor     :
            0.8 lag, unity
  Burden             :
            2.5, 7.5, 15 and 30 VA.
  Accuracy of adjustment : Within  i) + 3% of burden value.  

                                                   ii)
+ 2 electrical degree for angle. 

  C] precision current TRANSFORMER: 5 amps. & 1 amps.

  Primary          :            Wound : 5, 10, 15, 30 & 50 Amps.
                                      Bar      : By winding number of turns through center hole, following ranges can 
                                               achieved - 100, 200, 300, 400,500, 600, 1000, 1200, 2000A.

  Secondary      :
            5 Amps. & 1 Amps.
  Burden           :
            5 VA.
  Accuracy        :
            Class 0.1.
 
Voltage grade  :             600V
  Termination     :
            The wound primary & secondary will be terminated on suitable brass studs 
                                    duly marked. 
Construction      :
            The complete transformer will be housed within a polished wooden case 
                                    provided with center hole & carrying handle.

 
PT TEST SET

 
  A] PT TEST BRIDGE: 

  This test bridge is suitable for testing potential transformer having secondary voltage of 110V and 63.5V. 
  Input Voltage                   :            230V, 50Hz. , 1 phase AC. 
  Secondary voltage            :            110V and 63.5V. 
  Phase Angle Error Range     :            0 to + 20 minutes on x 1 range
                                           
                                                   
0 to + 100 minutes on x 5 range
                                             
                                                   
0 to + 400 minutes on x 20 range 

  Ratio Error Range               :            0 to  + 0.5% on x1 range
                                             
        0 to  + 2.5% on x5 range

                                                
     0 to  +10% on x20 range 

  Polarity Check                   :            Polarity indicated by lamp with "check" position selection.    
  Voltmeter                         :            One digital voltmeter to indicate the secondary voltage.  
 
  
Detector                          :
            A built-in detector of electronic type.

  Test Bridge having secondary voltage of 110V only is also manufactured. 

  B] burden box: 

  Rated current
               :            110V, 63.5V
  Power factor
                :            0.8 lag, unity
  Burden                        :
            5 to 200 VA in steps.
  Accuracy of adjustment : Within  i) + 3% of burden value.  

                                                   ii)
+ 2 electrical degree for angle.   

  C] precision potential TRANSFORMER

    Primary                     :
            33KV or 11KV 
    Secondary                 :
            110V / 63.5V
    Burden                      :
            5 VA.   
    Accuracy                   :
            Class 0.2
    System voltage           :
            33KV effectively earthen. 
    Termination                :
            HT & LT on suitable insulated terminals.  
    Type                         :
            Cast Resin Air Cooled with carrying handle. 
 

  D] precision potential TRANSFORMER

    Primary                      :            400, 660, 2200, 3300 or 6600V  by series parallel combination. 
    Secondary                  :
            110V  
    Burden                       :
            5 VA. 
    Accuracy                    :
            Class 0.2 
    System voltage            :
            6.6KV effectively earthen. 
    Termination                 :
            HT & LT on suitable insulated terminals. 
    Type                          :
            Cast Resin Air Cooled with carrying handle. 

Precision Potential Transformer of other Voltage, Burden & Accuracy class are also manufactured as per customers’ requirement. 

                                                 -----------Back to Top-----------

                                                Standard Instrument, CT & PT

precision current TRANSFORMER: 5 amps. & 1 amps. 

Primary             : Wound : 5, 10, 15, 30 & 50 Amps.
                              Bar : 
By winding number of turns through center hole, following ranges can achieved 
                                       - 100, 200, 300, 400,500, 600, 1000, 1200, 2000A.

Secondary        : 5 Amps. & 1 Amps.
Burden             : 5 VA.
Accuracy          : Class 0.1.
Voltage grade    : 600V 
Termination       : The wound primary & secondary will be terminated on suitable brass studs duly marked.

Construction      : The complete transformer will be housed within a polished wooden case provided with center hole & carrying handle. 

  
Current Transformer of other Current range, Burden & Accuracy class are also  manufactured as per  customers’ requirement.  

precision potential TRANSFORMER

Primary            : 33KV or 11KV 

Secondary        : 110V / 63.5V 
Burden             : 5 VA. 
Accuracy         : Class 0.2 
System voltage : 33KV effectively earthen. 
Termination      : HT & LT on suitable insulated terminals.  
Type               : Cast Resin Air Cooled with carrying handle.
 

precision potential TRANSFORMER

Primary            :  400, 660, 2200, 3300 or 6600V  by series parallel combination. 

Secondary        : 110V  
Burden             : 5 VA. 
Accuracy         : Class 0.2 
System voltage : 6.6KV effectively earthen. 
Termination      : HT & LT on suitable insulated terminals. 
Type               : Cast Resin Air Cooled with carrying handle. 
 

Potential Transformer of other Voltage, Burden & Accuracy class are also manufactured as per customers’ requirement.
                                                
-----------Back to Top-----------                               

                                                Burden Box for CT & PT 

burden box for CT:

Available in four sets

Rated current

Power Factor

Burden

Accuracy of adjustment

5 A

Unity

2.5, 7.5, 15, 30VA

Within  i) + 3% of burden value. ii) + 2 electrical degree for angle.

5A

0.8 lag

"

"

1A

Unity

"

"

1A

0.8 lag

"

"

Burden Box of other Burden & Accuracy class are also manufactured as per customers’ requirement. 

burden box for PT:

Available in four sets

Rated voltage

Power Factor

Burden

Accuracy of adjustment

110V

Unity

5 to 200VA in steps

Within  i) + 3% of burden value. ii) + 2 electrical degree for angle.

110V

0.8 lag

"

"

63.5V

Unity

"

"

63.5V

0.8 lag

"

"

Burden Box of other Burden & Accuracy class are also manufactured as per customers’ requirement.
                                   
                                                          
-----------Back to Top-----------

                                       CT KNEE POINT EXCITATION TEST SET
    
 

 
Input   : 230 Volts, 50Hz, single phase AC.

 
Output: Variable from 0 - 1000V AC, 1 phase, in 3-ranges i.e.
                          0 to 10 Volts AC at 2 Amps Max.                                           
                                              OR
                               0 to 100 Volts AC at 2 Amps. Max.                                                
                                              OR
                               0 to 1000 Volts at 1 Amps Max. 

 
Duty: 5 mins. ON & 15 mins. OFF.

 Metering:
         Digital Frequency Meter - 1no.
                        3 1/2 digit Digital Voltmeter having 3 ranges-1no.
                        3 1/2 digit Digital Ammeter having –1no.

 The set is provided with zero-start interlocking, overload and short circuit protection. 
 The Set also is provided with surge and harmonic suppressor to get quality AC voltage, which is a basic 
 requirement for this. 

 The set is a nice looking portable sheet steel cubicle.

 The set can also be available in automatic mode.


                                                         -----------Back to Top-----------  

               CT EXCITATION CURRENT CUM AC HIGH VOLTAGE TEST SET

Series: CTECAHV2; Type: 001K01A

The Test Set will be capable of measuring the following parameters of a CT based on Voltage Comparison Method.
 
 
i.    Magnetising Characteristic
 
ii.    CT Ratio
 
iii.    Polarity

 Input:   230 Volts, 50Hz., single phase AC.

 Output: Continuously variable in 4 ranges.

             
       0 to 40 V at 1.5 A Max.
             
       0 to 150V at 1.5 A Max.
             
       0 to 600V at 1.5 A Max.
             
       0 to 1000V at 1.0 A Max.
 Power supply Transformer is isolation type with electrostatic shielding.

 Duty:    5 mins. ON, 15 mins. OFF.

 Metering: 4½ digit Digital voltmeter used for measuring primary & secondary voltages.
              
4½ digit Digital ammeter used for measuring excitation current. 

 
  Hold facility is provided to freeze the readings on meters.
 Auxiliary D.C. Power supply and LED indicator is provided to detect the polarity of CT under Test.
 Microcomputer based version of this set is also available. 
                                                 --------------------------------

  Series: CTECAHV1; Type: 003K200m

  Input:   230 Volts, 50Hz., single phase AC.

  Output: Continuously variable in 4 ranges 

             
0 to 100 V at 2A Max.
             
0 to 1000V at 1A Max.
             
0 to 2500V at 0.5 A Max.
  and for AC High Voltage Test mode 0 to 3000V at 0.2 A Max. Tripping circuit at 50mA, 100mA & 200mA 
  provided.