Apart
from manufacturing the mentioned test sets, we also
manufacture equipment according to
specific requirements of
customer.
AC HIGH VOLTAGE TEST SET
DC HIGH VOLTAGE TEST SET
CABLE FAULT LOCATOR
CAPACITANCE & TAN-DELTA TEST SET FOR HIGH VOLTAGE EQUIPMENT
PARTIAL DISCHARGE TEST SET
MICRO OHM-METER
AC CURRENT INJECTION SET
MILLIVOLT DROP TEST SET
AC HIGH VOLTAGE SPARK TESTER FOR CABLE
NTPL"
make High voltage testing sets are suitable for Power
frequency AC high voltage test on transformers, motors,
insulators, cables etc. The sets are capable of giving
continuously variable AC HIGH VOLTAGE from zero to maximum
rated output voltage.

High
Voltage Test Set
(Oil Cooled) |

High
Voltage Test Set
(Dry Type) |
Input:
Generally,
230 Volts, 50Hz, single phase AC, upto 10KVA &
400/415V, two phase out of three
phases for sets beyond 10KVA.
However, we also manufacture AC H.V. sets workable on other
input voltage at extra cost.
Output: Continuously variable from zero to maximum rated
output voltage.
Capacity: Spread over a wide range of sets from 2.5KV to
300KV AC having capacities from several VA to hundreds of
KVA.
Duty cycle: Intermittent i.e., 5 minutes ON, 10 minutes
OFF. However, test sets of continuous or other duty
cycles can also be manufactured at extra cost.
Metering: Analog voltmeter & milliammeter/ammeter.
Digital meters may be provided at extra cost.
Protection: Tripping
mechanism for protecting the H.V. transformer against over
loading. The tripping mechanism can be adjusted at 25,50 &
100% of the rated current by a rotary switch. Below 100mA
&
above 20mA two adjustable tripping ranges are at 50%
&100%, while for sets of 20mA capacity or below only
100% is adjustable [If required by the users tripping
current can be made adjustable at other values, at extra
cost].
Apart from tripping mechanism, Zero start interlocking
along with Overvoltage alarm & indication are
provided.
Mode of operation: Sets are generally, motor operated
beyond 20KVA & 50KV. Motorisation facility can be
available below the specified value at extra cost.
H.V Transformer:
H.V.Transformer used for the testing purpose can be oil
cooled indoor type or Resin cast dry type as found
suitable or particularly required by the customer. The H.V.
winding of the high voltage testing transformers is of
graded insulation, one end of which is grounded through
milliammeter and tripping device while the other end remains
in floating condition as H.V. terminal. These testing
transformers are specially designed to withstand frequent intermittent
spark over or momentary short circuit conditions under which
such testing
transformers are supposed to operate.
Discharge Rod: For device under tests having large
capacitance, discharge rod may be provided at an extra
cost.
While sending enquiry for quotation or order please specify
the following:
Input voltage and frequency.
Maximum output voltage.
Capacity.
Type of transformer –Oil cooled or Cast Resin
Duty Cycle.
Mode of operation: Manual/Motor operated.
Any other details you find important to be specified.
-----------Back
to Top-----------
DC HIGH VOLTAGE TEST SET
|

DC High
Voltage Test Set
( Cascaded Type))
|

DC High Voltage Test Set
( In Two Units)
|
NTPL"
make High voltage testing sets are
suitable for testing electrical insulation of condensers, transformers,
motors, insulators, cables etc. The sets are capable of giving continuously variable DC HIGH VOLTAGE from zero to maximum
rated output voltage.
Input:
Generally, 230 Volts, 50Hz, single phase AC.
However, we also manufacture DC H.V. sets workable on other
input voltage at extra cost.
Output:
Continuously variable from zero to maximum rated output voltage.
Capacity:
Spread over a wide range of sets from 1 KV to 300KV with current
capacity upto 100mA.
Sets of higher current capacity can also be
manufactured.
Duty
cycle:
Intermittent
i.e., 5 minutes ON, 10 minutes OFF.
However, test sets of continuous or other duty cycles can
also be manufactured at extra cost.
Metering:
Output
DC high voltage measured by HV resistor chain along with
micro-ammeter scaled in kV.
Milli-ammeter to measure the leakage current.
Digital meters may be provided at extra cost.
Protection: Overload
& short circuit provided.
Zero start interlocking along with Overvoltage alarm & indication are provided.
Mode of operation:
Generally, sets
are manually operated. Motorisation facility can be available at extra cost.
Units:
Generally DC high voltage
test sets are available in one unit upto 35KV and sets of higher output voltage are commonly manufactured in two
units i.e. the control unit & Transformer–Rectifier unit. This Transformer–Rectifier
unit are made cascaded type above 80KV. However, NTPL always welcome customers' choice
regarding the no. of units.
Discharge rod:
A discharge rod is
provided with the set.
DC high voltage is generally obtained by simple rectification
of AC high voltage or by multiplication of relatively low AC high voltage by proper
multiplier circuits as is found suitable for a particular DC HV test set. HV transformers of
the Test Sets are Cast Resin types.
While
sending enquiry for quotation or order please specify the following:
Input voltage and frequency.
Maximum output voltage.
Capacity.
Duty Cycle.
Mode of operation: Manual/Motor operated.
Any other details you find important to be specified.
-----------Back
to Top-----------
underground cable fault locator
Cable Fault
Locator Bridge (Type-cflnt 02)
This
Test Set is capable to locate Short circuit faults, High Resistance
Earth faults that can be performed by H.V. D.C. source & Open
circuit faults in all types of L.T. & H.T. armored underground
cables (even P & T cables).

Cable Fault
Locator |
Features:
Detection by Null technique. Capable to overcome the
effect of cable capacitance & foreign potential.
Isolated
for High Voltage.
Power Source:
External
Power source of 12 volts DC nominal, capable to deliver 100mA
current is
supplied along with the locator.
For Short circuit fault detection:
Current measurement 100mA with input Impedance selection in multiple
ranges.
Open circuit Fault detection:
Capacitance Bridge technique.
Cable
Fault Locator Bridge may be provided with the following additional:
Additional
(1): AC
Mains cum Battery Operated DC HV Power Supply
Series- DHVMCBPS (Type- 2K5V050m)
Input : 230 V, 50Hz,single phase AC mains & built-in
rechargeable battery.
Output: 25
Volts to 2500 volts DC. Max.capacity - 50mA with built-in short
circuit protection.
Additional
(2): Surge
Generator cum DC HV Test Set for Testing & Burning Faults
(Type
- SGNT14)
Apart from
providing output voltage for DC High Voltage testing, the surge
generator cum DC HV test kit
is designed to produce single as well
as repetitive high-energy surges and can be used in conjunction
with Cable Fault Locator.
Input:
220/240 volts, 50Hz, 1KVA, approx.
Output:
Continuously variable from (i) 0 to 3.5KV DC,
(ii) 0 - 7.0 kV DC & (iii) 0 - 14 kV DC.
Maximum
Current:
150mA at 3.5 kV range,
80mA at 7.0 kV range &
50mA at 14 kV range.
Features:
Low input power.
Automatic
discharge of internal capacitor and circuit under test if mains
supply switched off.
Controls
interlocked for complete safety.
A
key operated safety switch prevents unauthorized operation of the
model SGNT14.
Additional
(3): Cable Fault Burner (Type -CFBNT)
To detect
fault resistance higher than 10 Mega ohms CFBNT is suitable to burn
down the faulty cable
relatively to a low resistance fault.
Input : 230 volts, 50Hz, single phase AC.
Output : Continuously variable from 0 to 10KV.
Capacity
: Burning current upto 50mA. Output is
featured with drooping characteristic to have better
control on over
burning.
Additional
(2) or Additional (3) can be selected alternatively.
Additional
(1), Additional (2) & Additional (3) are provided with-
Metering
for output voltage & current measurement.
Overload
tripping mechanism, Over voltage indication lamp & buzzer will
be provided.
Zero
start inter locking will be provided to ensure that the H.V. circuit
cannot be energized unless the
regulator is first returned to zero
position.
Additional
(4): Thyristor Thumper (Type-NTTTH01)
Single
or repetitive fault can be re-energized by a switch for a preset
length of time usually 10 cycles.
If the current crosses the highest
current level before the completion of 10 cycles, the current
injection
is switched off to avoid unnecessary over burning of the
cable under test. The set can also be operated
in a single shot
mode.
The
Set is used to pin point faults particularly for low voltage cables.
Input:
230V, single phase, 50Hz., AC.
Output:
50Amps max.
Features:
Safety
interlocks are provided
Low
Power is required.
-----------Back
to Top-----------
Capacitance
& Tan-Delta Measuring Equipment along with its accessories
is suitable for testing motors,
Power Transformers, H.V.
Bushings, Generators, Power Capacitors, cables etc. at power
frequency. Periodic
measurement of dissipation factor &
capacitance on new solid insulators and those on long service
period
produces comparative result about the trend of
deterioration of insulation resistance before insulation
breakdown occurs.
Thus,
the set is ideal to conduct routine diagnostic tests on solid
insulating components, equipment
required for High Voltage
generation, Transmission and Distribution.
The
Set is in four units:
i. Capacitance & Tan-Delta Measurement Bridge
ii. High Voltage AC Power Supply Control Unit
iii. High Voltage AC Power Supply Transformer Unit
iv. Standard Capacitor
|

Capacitance
& Tan-Delta Test Set |
Standard test modes
1.
UST -
UNGROUNDED SPECIMEN TEST.
Reduces
the effect of stray capacitance to ground. Maximum accuracy is
obtained in this mode.
2.
GST -
GROUNDED SPECIMEN TEST.
Mostly
used in outdoor installations, power systems when the object under
test is permanently
grounded. Exp. Windings of Transformer to tank
and core, Coils of Rotating machine, circuit breaker
assembly etc.
3. GST-G – GROUNDED SPECIMEN TEST WITH GUARD.
Performed
to measure stray capacitance and separate it from values obtained in
GST test.
Capacitance & Tan-Delta Measurement Bridge
Type
Test Voltage Current
Capacity
CTDNTE12
0-12KV 200mA
Max.
CTDNTE20
0-20KV
2A Max.
Input:
230Volts, single phase, 50Hz. AC.
Capacitance
measurement:
Value
of Standard
Cx x four
Resolution
Accuracy
Capacitor
(Cs) used
multiplier range
------------------------------------- ------------------------------
--------------------- -------------------------------------------
100 pF
1 pF to 0.11 mF
0.1 pF
+ 0.2% of reading + .1 pF
1000
pF (1 nF)
10 pF to 1.1 mF
1 pF
+ 0.2% of reading + 1 pF
10000 pF (10 nF)
100 pF to 11 mF
10 pF
+ 0.2% of reading + 10 pF
Tan
– Delta measurement:
Tan-Delta
Tan-Delta
Resolution
Accuracy
Factor
Range
---------------- --------------------------
----------------------
-------------------------------------------
0.1
1 x 10-4 to 0.11
2 x 10-6
+ 2% of reading + 2 x10-5
1.0
1 x 10-3 to 1.11
2 x 10-5
+ 1% of reading + 2 x10-4
10.0
1 x 10-2 to 11.1
2 x 10-4
+ 1% of reading + 2 x10-3
Special
shielding arrangement has been designed for this kit to suppress
external interference. These
enable accurate measurements even in
electrically noisy environment particularly in switchyards.
High Voltage AC
Power Supply
Input:
415Volts, two phase out of three phase, 50Hz. AC.
Series Type
Test Voltage Current
Capacity
Duty Cycle
ACHVCTD 12K200m
0-12KV
200mA 15 mins.
100mA
continuous
ACHVCTD
20K2A
0-20KV
2A
30 mins.
1.5A
60mins.
1A
continuous
Metering:
31/2
digital panel voltmeter & ammeter
Standard
Capacitor
Wide
range of NTPL Standard capacitors are load loss stable capacitors
designed for use with Capacitance
& Tan -Delta Bridge.
|
Series
:
STCCTD.
|
|
Type
: 100P12K
100P20
1000P/12
1000P/20 10n12K
10n20K
|
|
Capacitance
: 100PF+5%
100PF+5%
1000PF+5%
1000PF+5%
1nF+5%
10nF+5%
|
|
Operating
voltage :
12KV 20KV
12KV
20KV 12KV
20KV
|
|
Max.
voltage : 14.5KV
24KV
14.5KV
24KV
14.5KV
(1min)
|
|
Frequency
of
: 50Hz
+
10%
operation
|
|
Actual
value of
:
Actual value indicated on capacitor.
Capacitance
|
Additional
at extra cost
Range
extension current transformer
Reactor
Sets
at other test voltages, capacity, measurement ranges can also be
manufactured on request of customer.
-----------Back
to Top-----------
PARTIAL DISCHARGE test set
type:
pdnt02
This
Test Kit is used for non-destructive means of assessing the quality
of high voltage transformers, motors, cables etc., which are used
in generation & distribution of electric power.
The basic system consists of-
Discharge
measuring module
Input : 230volts,
50Hz., single phase AC.
Measuring
Range:
0
to 5,50,500,5000pC in different switchable ranges.
Discharge pulses can be detected and measurement can be
done in analog scale
as well as in PC.
MATCHED
MEASURING IMPEDANCE
In series with standard capacitor this forms
a voltage divider and decouples the high frequency signals to
feed the discharge measuring module. The
set is electro statically shielded.
Standard
Capacitor: 100pf
or 1000 pf.
C.R.O.
suitable for the above
Calibrating
Pulsar
OPTIONAL
AT EXTRA COST:
40
kV AC
high Voltage measuring system
Auxiliary
Supply Voltage: 230 Volts, 50Hz, single phase, AC.
Range: 0 - 40 kV AC
Metering: 31/2 digital panel meter.
-----------Back
to Top-----------
MICRO
OHM-METER
(Type:
UONT100A)
This Test Set is capable to measure low resistance like
switch contacts, breaker contacts, busbar splices, joints, fuses, low inductive windings etc. by
circulating high value of D.C. through the contact/junction and
measuring D.C voltage drop (4 terminal method) which, sent to instrument amplifiers , thereby being displayed on
resistance meter.
|

Micro-Ohm
Meter |
|
Technical Features:
|