Description
“NTPL” MAKE 60 KV DC Vacuum Bottle Test Set Model – VINT60KV
APPLICATION:
Suitable for testing the condition of vacuum bottle in medium voltage switchgear. Leakage current preset value (GO/NO-GO) adjustable from 0.2mA to 2mA using LCD & Keypad. Red & Green lamp indication for defective and acceptable bottle.
Technical Features:
Input Power Supply : 230V ± 10%, 50Hz ± 5%, 1 Phase AC.
Output Test Voltage : Continuously variable from 0 to 60 KV DC.
Max. output current : 2.5mA max. at HT side.
Leakage current Limit : Pre-settable from 0.2 to 2mA for GO/NO-GO testing.
Duty : Intermittent duty cycle, i.e., 5 mins ON, 10 mins. OFF.
Transient Protection : 2.5mA(Instantaneous trip through fast acting DC relay)
Output Ripple voltage : <3% at no load.
Operating Temperature : 0-50°C
Feature:
- Power Mains ON – OFF switch & Fuse.
- ‘HT’ ON & ‘HT’ OFF push buttons.
- Lamp indication: Power Mains ON, HT ON, ACCEPTABLE (Green), DEFECTIVE (Red) ,OVERVOLTAGE.
- Knob for continuous variation of the output test voltage up to the required voltage level.
- 4-Key matrix keyboard for setting of test parameters.
- Resistive self-discharging.
- Transient Tripping current set at 2.5mA.
- Last applied test voltage latched & indicated in the LCD on tripping of HT circuit.
Metering: The LCD will indicate the status…..
Voltage in KV, leakage current in mA, Test time (Dwell time)
- Accuracy of voltage measurement : ± 3% of FS, Resolution: 0.1kV.
- Accuracy of leakage current measurement : ± 3% of FS Resolution: 0.01mA.
Protection & Interlock:
- Zero start interlock
- Automatic tripping mechanism against over loading.
- Over voltage Indication.
DC High Voltage Assembly Unit:
- HV Transformer & DC HV Block mounted on MS trolley within Insulated jacket.
- The Transformer & DC HV Block cast resin type.
- Designed to withstand frequent intermittent spark over or short circuit conditions
- Series resistance to limit inrush of current at the output.
Accessories:
- 3-pin Input Power cord with plug-3M – 1 No.
- Interconnecting cables between the units-3M – 1 No.
- Discharge rod with grounding cable-5M – 1 No.
- Ground cable-3M – 2 Nos.
- High voltage return cable of minimum length-5M. – 2 Nos.
- Carrying case/bag for accessories. – 1 No.
Documents:
- Operation Manual(Instruction Manual)
- Works Test Report
- Warrantee Certificate
Reviews