PRIMARY CURRENT INJECTION SET

APPLICATION:

During installation, testing, especially if the protective gear is connected to the power line via a current transformer it is advisable to use our Primary Current Injection Set. Thus, wide range of Primary Current Injection Sets are being manufactured by “NTPL”.

These sets have been designed to enable the users of heavy electrical equipment to carry out such tests as have previously been described with a maximum efficiency at minimum cost, providing a convenient means of delivering, controlling and measuring a heavy current in a comparatively low voltage low impedance circuit. A set like this is ideal for routine testing of circuit breakers, current transformers with or, without ammeter and can be used for many other applications where a heavy current supply of short duration is required

Description

“NTPL” MAKE 300A/5V PRIMARY CURRENT INJECTION SET

SERIES: PCNT3R

TYPE: 300A05V

 

TECHNICAL FEATURES:

Input                :           230 Volts, single phase, 50Hz, AC.

Output             :            A) Current output:       Continuously variable from

0-300 Amps at 5 Volts (Open circuit voltage).

Or

0-150 Amps at 10 Volts (Open circuit voltage).

Or

0-75 Amps at 20 Volts (Open circuit voltage).

B) Voltage Output: 0-250V, 1ph., 50Hz., Max. Capacity: 4A Either current output or voltage output mode selectable at a time.

Duty           :                Intermittent i.e. 5 minutes ON, 10 minutes. OFF.

 

The above test kit will be in single unit provided with wheels for easy movement.

  • Power Mains ON – OFF operation is done by means of an ON – OFF switch & Fuse or by MCB along with ‘ON’ lamp indication.
  • Control START-STOP push along with ‘START’ lamp indication to energise the control
  • Continuously variable autotransformer providing smooth control from zero to maximum rated current.
  • Digital Ammeter connected in the secondary circuit of the current transformer, giving reading of loading current in % of the range. Resolution: 0. 1
  • Automatic tripping mechanism for protecting the Loading transformer against over loading. After tripping, output current will be switched OFF.
  • The variable voltage source to the current loading transformer provided can also be used separately to obtain a variable voltage output source which can be utilized for many other purposes. This voltage will be indicated by a digital
  • Digital Time Interval Meter, for measurement of time during the operation of protective relays is very important and a Time Interval Meter can measure this time. For this “NTPL” make Digital Time Interval meter is

Measuring Range                     Resolution

0-9.999secs.                                 0.001sec.

0-99.99secs.                                  0.01sec.

  • Display: Seven segment
  • Accuracy: +1%.
  • Terminals to relay
  • Reset push
  • Selector for NO & NC
  • START’ Timer with opening of Potential free
  • Input cable / plug & socket

The whole control circuitry & loading unit will be housed within a well-ventilated sheet metal cabinet treated properly and powder coated. All control knobs, switches, terminals, meter etc. are mounted on the top panel, which can be approached by opening the hinged lid. The output terminals are to be fitted at the rear of the cabinet.

 

LOADING TRANSFORMER:

  • Double wound air cooled type loading transformer with secondary winding sections arranged for different output current ranges, selectable by proper series parallel links connections.
  • Current Transformer & its secondary terminals.
  • Heavy current output terminals.

 

DOCUMENTS:

Operation Manual, Works Test Report, Warrantee Certificate will be supplied along with the set.

 

NOTE: The above specification does not include High Current Output cable.